IP House | Technical Specification
Designed and built to Tier III standards, with multiple levels of redundancy across all critical systems, we guarantee unrivalled service availability.
15624
page-template,page-template-full_width,page-template-full_width-php,page,page-id-15624,page-child,parent-pageid-15641,qode-quick-links-1.0,ajax_fade,page_not_loaded,,qode-title-hidden,hide_top_bar_on_mobile_header,qode-child-theme-ver-1.0.0,qode-theme-ver-13.8,qode-theme-bridge,disabled_footer_bottom,wpb-js-composer js-comp-ver-5.4.7,vc_responsive

Technical Specification

Designed and built to Tier III standards, with multiple levels of redundancy across all critical systems, we guarantee unrivalled service availability.

GENERAL
Total AreaApproximately 16,000ft2
Fully Developed Technical AreaApproximately 14,000ft2
Floor LoadingPoint loading of computer floor 450kg
CarriersCloud and Carrier Neutral including: BT, Zayo, euNetworks, Level3, Colt, Vodafone, Six Degrees Group and Virgin
ConnectivityLAN/WAN connectivity at native speeds, Internet 1mb upward to multi GigE, Metro connectivity and fibre routes to a number of Data Centres including THN

MECHANICAL INFRASTRUCTURE
Environment Control21 degrees C±3 degrees C and humidity at 50% ± 10% with cooling load per rack of 4kW at full occupancy
Air Conditioning SystemDenco DX
Room Cooling Units70Kw down flow handlers (pressurized raised floor)
FeatureN+1 configuration (Each AHU is independent)

ELECTRICAL INFRASTRUCTURE
Utility SupplyDedicated utility incomer feeding dual HV distribution
Standby Diesel GeneratorDual FG Wilson
Standby Generator Capacity2x 980Kva
Operational Capacity24h fuel storage with fuel delivery callout contract in place, 14,000 litre separate tank
UPSAPC Symmetra PX
UPS CapacityN+1, 4 x 500 kVA with infrastructure to add more units as load requires
Autonomy Period10 minutes at full rated load
Power to EquipmentUPS protected, dual supplies to each rack. Intelligent 0u in-rack mounted power strips to standard outlets

FIRE DETECTION & SUPPRESSION
GeneralSystem comprises of 3 stage detection
First Stage DetectionSmoke detectors
Second and Third Stage DetectionFully addressable analogue alarm system. Double knock condition will initiate gas release
Gas SuppressionFM200

SECURITY
Manned Security24 x 7 x 365 security cover
CCTVCoverage of external/internal areas, including Data Centre suites and authorized access areas
Access ControlAccess card authentication
Site AccessMulti-stage authentication before gaining access to facility

CONTROL SYSTEMS
Building ManagementAlarm monitoring system; reports on electrical, mechanical, temperature, humidity, fire, leaks, security and access control
DeliveryLorry access to delivery point. Facilities provided: secure delivery storage and build and test suite